The full Table B.4.2.1-1, searchable.

Photo: Sven Mieke / Unsplash

In Table B.4.2.1-1 the NSR-10 sets the minimum live loads to be used in design according to the use of each space: for example, 1.8 kN/m² in private rooms of dwellings, 2.0 kN/m² in offices and 5.0 kN/m² in retail. The design must use the maximum load expected from the use, never less than these minimums (B.4.2.1).

NSR-10 Table B.4.2.1-1: minimum uniformly distributed live loads, per m² of plan area.
UseSpacekN/m²kgf/m²
AssemblyBalconies5.0500
AssemblyCorridors and stairs5.0500
AssemblyFixed seating (fastened to the floor)3.0300
AssemblyGyms5.0500
AssemblyLobbies5.0500
AssemblyMovable seating5.0500
AssemblyRecreation areas5.0500
AssemblyPlatforms5.0500
AssemblyStages7.5750
OfficesCorridors and stairs3.0300
OfficesOffices2.0200
OfficesRestaurants5.0500
EducationalClassrooms2.0200
EducationalCorridors and stairs5.0500
EducationalLibraries: reading rooms2.0200
EducationalLibraries: stacks7.0700
FactoriesLight industry5.0500
FactoriesHeavy industry10.01000
InstitutionalOperating rooms, laboratories4.0400
InstitutionalPrivate rooms2.0200
InstitutionalCorridors and stairs5.0500
CommercialRetail5.0500
CommercialWholesale6.0600
ResidentialBalconies5.0500
ResidentialPrivate rooms and their corridors1.8180
ResidentialStairs3.0300
StorageLight6.0600
StorageHeavy12.01200
GaragesPassenger cars2.5250
GaragesTrucks of up to 2,000 kg capacity5.0500
Arenas and stadiumsGrandstands5.0500
Arenas and stadiumsStairs5.0500

How is the table used?

Each space is designed for the load of its use. Several coexist in one building: a residential building uses 1.8 kN/m² in the apartments, 3.0 kN/m² in the stairs and 5.0 kN/m² on the balconies. If the intended use produces larger loads, such as racking or equipment, the design must use those real loads.

What if the use changes?

Turning a house into offices, an apartment into a shop or an office mezzanine into storage changes the design load. The NSR-10 requires the structure to be reviewed when the use changes (A.10.1.3.2).

And roofs?

Roofs have their own table, B.4.2.1-2: a usable roof or terrace takes the load of the rest of the building, and a roof used as a garden or for gatherings, 5.0 kN/m².

Frequently asked questions

What is the residential live load in the NSR-10?

1.8 kN/m² (180 kgf/m²) in private rooms and their corridors, 3.0 kN/m² on stairs and 5.0 kN/m² on balconies (Table B.4.2.1-1).

What is the live load for offices?

2.0 kN/m² in offices, 3.0 kN/m² in corridors and stairs and 5.0 kN/m² in restaurants (Table B.4.2.1-1).

And for a warehouse?

Light storage 6.0 kN/m² and heavy storage 12.0 kN/m². With tall racking or forklifts, the design must use the real loads if they are larger.

Can I design for a lower load than the table?

No. The values in the table are minimums: design live loads may in no case be lower (B.4.2.1).